To fix a ACB into a position (Dis-connected, Test, Connected)
* Standard offer in the draw-out type
To indicate the position (Dis-connected, Test, Connected)of a ACB
* Standard offer in the draw-out type
Rated voltage(V) | Operational voltage (V) | Inrush current peak value(A) | Steady current(A) | Closing time(sec) | |
---|---|---|---|---|---|
AC/DC 50/60Hz |
110 | 94-121 | 2 | 1 | 0.08 Under |
220 | 187-242 | 3 | 1.3 | ||
DC | 125 | 106-138 | 2.3 | 1 | |
24 | 21-26V | 30 | 3.5 | ||
48 | 41-53V | 30 | 7 |
Note
Rated voltage(V) | Operational voltage (V) | Inrush current peak value(A) | Steady current(A) | Closing time(sec) | |
---|---|---|---|---|---|
AC/DC 50/60Hz |
110 | 77-121 | 2 | 1 | 0.04 Under |
220 | 154-242 | 3 | 1.3 | ||
DC | 125 | 88-138 | 2.3 | 1 | |
24 | 21-26V | 30 | 3.5 | ||
48 | 41-53V | 30 | 7 |
Note
TYPE | OCR-II | OCR-III |
---|---|---|
Operational type | Momentary operation type (Under 15ms) | Magnetic maintenance type |
Formation of contact | 2NO | 2NO |
Condition of circuit breaker | Cause of trip | Condition of "a" contact |
---|---|---|
TRIP | Long-time delay trip, Short-time delay trip, Instantaneous-time delay trip, Ground fault trip |
ON |
Trip button, Shunt trip coil (SHT), Undervoltage trip (UVT) |
OFF | |
ON | OFF | |
OFF | OFF |
TYPE | Capacity | |
---|---|---|
Ratings | AC | 250V 5A |
DC | 30V 5A | |
Rated current | 5A | |
Maximum contact voltage | AC | 380V |
DC | 125V | |
Maximum contact current | 5A | |
Minimum applicable load | DC | 5V 10mA |