SJ700D Series(0.4kW-55kW), 3-phase 200V class Standard Specifications

Model SJ700D- US Version 004LFUF3 007LFUF3 015LFUF3 022LFUF3 037LFUF3 055LFUF3 075LFUF3 110LFUF3 150LFUF3 185LFUF3 220LFUF3 300LFUF3 370LFUF3 450LFUF3 550LFUF3
Enclosure *1 IP20 IP00
Applicable motor (4-pole, kW(HP)) *2 CT *6 0.4(1/2) 0.75(1) 1.5(2) 2.2(3) 3.7(5) 5.5(7.5) 7.5(10) 11(15) 15(20) 18.5(25) 22(30) 30(40) 37(50) 45(60) 55(75)
VT *6 0.75(1) 1.1(1.5) 2.2(3) 3.0(4) 5.5(7.5) 7.5(10) 11(15) 15(20) 18.5(25) 22(30) 30(40) 37(50) 45(60) 55(75) 75(100)
Output Ratings Rated capacity
(KVA)
200V CT *6 1.0 1.7 2.5 3.6 5.7 8.3 11 15.9 22.1 26.3 32.9 41.9 50.2 63 76.2
VT *6 1.2 2.1 3.2 4.1 6.7 10.3 15.2 20.0 25.2 29.4 39.1 48.4 58.5 72.7 93.5
240V CT *6 1.2 2.0 3.1 4.3 6.8 9.9 13.3 19.1 26.6 31.5 39.4 50.2 60.2 75.6 91.4
VT *6 1.5 2.6 3.9 4.9 8.1 12.4 18.2 24.1 30.3 35.3 46.9 58.1 70.2 87.2 112.2
Rated output current (A) CT *6 3 5 7.5 10.5 16.5 24 32 46 64 76 95 121 145 182 220
VT *6 3.7 6.3 9.4 12 19.6 30 44 58 73 85 113 140 169 210 270
Overload capacity (output current) CT : 150%,60sec., 200%,3sec.
VT : 120%,60sec., 150%,5sec.
Rated output voltage *3 3-phase (3-wire) 200 to 240V (corresponding to input voltage)
Input Rating Rated input voltage (V) 3-phase 200 to 240V+10%, -15%, 50/60Hz±5%
Rated input current (A) CT *6 3.3 5.5 8.3 12 18 26 35 51 70 84 105 133 160 200 242
VT *6 3.9 7.2 10.8 13.9 23 37 48 64 80 94 120 150 186 240 280
Braking Dynamic braking (Short-time) *4 Built-in BRD circuit (optional resistor) External dynamic braking unit(option)
Minimum value of resistor (Ω) 50 50 35 35 35 16 10 10 7.5 7.5 5 —
Vibration *5 5.9m/s2(0.6G), 10~55Hz 2.9m/s2(0.3G), 10~55Hz
Integrated EMC filter Built-in(EN61800-3 category C3)
Zero-phase Reactor Built-in
Weight (lbs.) 3.5(7.7) 3.5(7.7) 3.5(7.7) 3.5(7.7) 3.5(7.7) 6(13.2) 6(13.2) 6(13.2) 14(30.8) 14(30.8) 14(30.8) 22(48.4) 30(66) 30(66) 43(94.6)
*1
The protection method conforms to JIS C 0920(IEC60529).
*2
The applicable motor refers to Hitachi standard 3-phase motor (4-pole).
To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3
The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4
Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5
Conforms to the test method specified in JIS C 60068-2-6:2010(IEC 60068-2-6:2007).
*6
In case of driving light load application, be able to choose a low capacity inverter. CT and VT is the abbreviation of constant torque mode and variable torque mode.